Power Cables | ||||||||||||||
Power Cables
BS 6622 Single Core Armoured 15KV XLPE Stranded Copper Conductors
Construction
Cross-sectional area mmsq |
Minimum average thickness of insulation mm |
Nominal area of copper tape screen mm sq |
Nominal thickness of PVC bedding |
Nominal number and diameter of armoured wires no./mm |
Nominal thickness of PVC oversheath |
Nominal overall diameter of cable mm |
50 |
4.5 |
19.4 |
1.2 |
43/1.6 |
1.9 |
30.3 |
70 |
4.5 |
21.2 |
1.2 |
46/1.6 |
1.9 |
32.1 |
95 |
4.5 |
22.9 |
1.2 |
40/2.0 |
2.0 |
34.8 |
120 |
4.5 |
24.4 |
1.2 |
42/2.0 |
2.1 |
36.5 |
150 |
4.5 |
25.7 |
1.2 |
44/2.0 |
2.1 |
37.8 |
185 |
4.5 |
27.5 |
1.2 |
46/2.0 |
2.2 |
40.0 |
240 |
4.5 |
29.7 |
1.2 |
49/2.0 |
2.3 |
42.4 |
300 |
4.5 |
32.0 |
1.2 |
53/2.0 |
2.3 |
44.7 |
400 |
4.5 |
34.7 |
1.3 |
46/2.5 |
2.5 |
49.0 |
500 |
4.5 |
37.6 |
1.3 |
49/2.5 |
2.6 |
52.1 |
630 |
4.5 |
41.0 |
1.4 |
53/2.5 |
2.7 |
55.9 |
800 |
Please refer to our technical department for further information |
|||||
1000 |
Installation
Cross-sectional area mmsq |
Approximate cable weight kg/m |
Nominal drum length |
Minimum bending radius mm |
Nominal internal diameter of ducts mm |
50 |
1.4 |
1000 |
550 |
100 |
70 |
1.7 |
1000 |
600 |
100 |
95 |
2.1 |
500 |
650 |
100 |
120 |
2.4 |
500 |
700 |
100 |
150 |
2.7 |
500 |
700 |
100 |
185 |
3.2 |
500 |
750 |
100 |
240 |
3.8 |
500 |
800 |
100 |
300 |
4.5 |
500 |
850 |
100 |
400 |
5.6 |
300 |
900 |
100 |
500 |
6.7 |
300 |
950 |
100 |
630 |
8.2 |
300 |
1050 |
100 |
800 |
Please refer to our technical department for further information |
|||
1000 |
Electrical Performance
Cross-sectional area mmsq |
Maximum DC resistance of conductor at 20 ℃ uohms/m |
Maximum AC resistance of conductor at 90 ℃ uohms/m |
Reactance at 50Hz |
Impedance at 50Hz uohms/m |
Maximum Capacitace PF/m |
Maximum charging current at normal voltage and frequency mA/m |
50 |
387 |
494 |
144 |
514 |
204 |
0.56 |
70 |
268 |
343 |
135 |
368 |
232 |
0.63 |
95 |
193 |
248 |
129 |
279 |
258 |
0.7 |
120 |
153 |
196 |
124 |
232 |
281 |
0.77 |
150 |
124 |
159 |
121 |
198 |
301 |
0.82 |
185 |
99.1 |
128 |
117 |
172 |
329 |
0.9 |
240 |
75.4 |
98 |
113 |
148 |
363 |
0.99 |
300 |
60.1 |
80 |
108 |
133 |
398 |
1.09 |
400 |
47 |
64 |
107 |
124 |
439 |
1.2 |
500 |
36.6 |
51 |
103 |
114 |
483 |
1.32 |
630 |
28.3 |
42 |
99.5 |
107 |
534 |
1.46 |
800 |
Please refer to our technical department for further information |
|||||
1000 |
Ratings
Cross-sectional area |
Current Ratings |
Short circuit ratings |
|||
Laid direct in ground |
Drawn into ducts |
650Laid in air |
One second short circuit rating of conductor |
One second short circuit rating of copper per core |
|
50 |
220 |
220 |
250 |
6.8 |
Typically less then 1kA |
70 |
270 |
260 |
310 |
9.8 |
|
95 |
320 |
305 |
375 |
13.3 |
|
120 |
360 |
640 |
430 |
17.2 |
|
150 |
410 |
375 |
490 |
21.2 |
|
185 |
455 |
410 |
550 |
26.6 |
|
240 |
520 |
460 |
650 |
34.9 |
|
300 |
580 |
500 |
740 |
43.8 |
|
400 |
650 |
530 |
840 |
57.3 |
|
500 |
710 |
570 |
930 |
72.3 |
|
630 |
760 |
620 |
1040 |
91.2 |
|
800 |
Please refer to our technical department for further information |
||||
1000 |